Skip to main content
Siemens 3VA1216-5EF32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1216-5EF32-0HA0 SENTRON MCCB, 160 A, 3-Pole, 187

MPN3VA1216-5EF32-0HA0

Siemens SENTRON 3VA1216-5EF32-0HA0, molded case circuit breaker, line protection, 3-pole, 160 A, breaking capacity 187 kA at 240 V AC, TM240 overcurrent release, shunt trip, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1216-5EF32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1216-5EF32-0HA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C155.6 A
Current at 60 °C151.2 A
Current at 65 °C146.8 A
Current at 70 °C142.4 A
Switching capacity classS
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V36 kA
Breaking capacity at 690 V17 kA
3VA1216-5EF32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1216-5EF32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1216-5EF32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1216-5EF32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1216-5EF32-0HA0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

Siemens 3VA1216-5EF32-0HA0 — 160 A SENTRON MCCB with TM240 release and shunt trip

Breaking capacity is specified at multiple voltage levels: 187 kA at 240 V AC, 121 kA at 415 V AC, 36 kA at 440 V AC, and 17 kA at 690 V AC. Current rating holds at 160 A from 40 °C through 50 °C, then derates linearly to 142.4 A at 70 °C. The thermal curve matters for panel builders packing breakers into a confined enclosure — if the ambient inside the panel runs above 50 °C, the effective continuous current drops. Plan the load accordingly.

Dimensions: 105 mm wide, 158 mm high, 70 mm deep. No auxiliary contact version is fitted as standard; the only integrated auxiliary is the shunt trip. If the BOM calls for any of those, this variant is the wrong pick — the shunt trip alone covers remote tripping via a control signal.

Frequently asked questions

Where can I buy 3VA1216-5EF32-0HA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1216-5EF32-0HA0 at different voltages?

Breaking capacity is 187 kA at 240 V AC, 121 kA at 415 V AC, 36 kA at 440 V AC, and 17 kA at 690 V AC.

Does 3VA1216-5EF32-0HA0 include an undervoltage release or communication?

No. It has no undervoltage release, no communication function, no phase failure detection, and no ground fault monitoring. The only auxiliary release is the shunt trip.

MPN
3VA1216-5EF32-0HA0