Siemens 3VA1216-5EF32-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1216-5EF32-0KA0 SENTRON MCCB, 160 A, 3-Pole, Shun

MPN3VA1216-5EF32-0KA0

Siemens SENTRON 3VA1 molded case circuit breaker, 3VA1216-5EF32-0KA0, 160 A at 40 °C, 3-pole, TM240 thermal-magnetic release, shunt trip (STL), 187 kA interrupting at 240 V, 70 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1216-5EF32-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12165EF320AA0
3VA1216-5EF32-0KA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C156 A
Current at 60 °C151 A
Current at 65 °C147 A
Current at 70 °C142 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.33 W
3VA1216-5EF32-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1216-5EF32-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1216-5EF32-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1216-5EF32-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1216-5EF32-0KA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width105 mm
Depth70 mm
Height (in)6.22 in
Width (in)4.13 in
Depth (in)2.76 in

Product details

SENTRON 3VA1 molded case circuit breaker, 160 A, shunt trip

Siemens 3VA1216-5EF32-0KA0 is a SENTRON 3VA1 MCCB rated 160 A at 40 °C, 3-pole, with TM240 release and shunt trip (STL). Rated insulation voltage is 800 V, and the breaker maintains full 160 A current rating through 50 °C, derating to 156 A at 55 °C and 142 A at 70 °C. Maximum power loss is 33 W.

The 105 mm width occupies a standard three-pole MCCB footprint; verify the existing panel cutout accommodates the 158 mm height and 70 mm depth before ordering. The shunt trip (STL) requires a separate control voltage — confirm polarity and voltage rating from the auxiliary release datasheet, as the shunt trip coil is polarity-sensitive. The TM240 release is not field-interchangeable; the breaker is ordered as a complete assembly.

Interrupting capacity by voltage

Interrupting capacity varies significantly with system voltage: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V. For 480 V applications (common in North America), the 75.6 kA at 440 V is the closest published figure — actual 480 V performance is not listed but typically interpolates between the 440 V and 500 V values. Selectivity coordination studies should use the published values for the specific system voltage.

Frequently asked questions

What compliance documentation does this brand provide for 3VA1216-5EF32-0KA0?

Siemens provides IEC/UL datasheets, CE declaration, RoHS and REACH compliance statements for the SENTRON 3VA1 series. Specific documentation for this order code is available on request.

MPN