MCCB for high-fault panel protection
The interrupting capacity at 240 V is 220 kA, dropping to 154 kA at 415 V and 121 kA at 440 V — figures that tell you this breaker is sized for high-fault installations where upstream transformer capacity is substantial.
Thermal-magnetic curve and temperature derating
The overcurrent release is a TM240 thermal-magnetic unit. At 55 °C and 60 °C it derates to 24 A, and at 65 °C and 70 °C to 23 A.
Pole count, auxiliary switches, and trip options
This is a 4-pole MCCB with 100% N-conductor protection — the neutral pole is fully rated, not just a switched neutral. The integrated shunt trip (STL) release, order code 3VA9688-0BL33, allows remote tripping via a control signal.
Physical fit and mounting
Height is 130 mm; width is 4 in. The 4-pole footprint matches the standard SENTRON 3VA 4-pole cutout — if you are replacing an existing 3VA or a competitor's 4-pole MCCB, verify the busbar spacing and terminal center-to-center distances against the panel layout before ordering. The auxiliary switch wiring exits the front; plan your wireway clearance accordingly.