Skip to main content
Siemens 3VA1216-6GF42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1216-6GF42-0AA0 SENTRON MCCB, 160 A, 4-Pole, 220

MPN3VA1216-6GF42-0AA0
Active

Siemens SENTRON 3VA1216-6GF42-0AA0, molded case circuit breaker, 4-pole, 160 A rated current, TM240 thermal-magnetic release, interrupting capacity 220 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1216-6GF42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1216-6GF42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C156 A
Current at 60 °C151 A
Current at 65 °C147 A
Current at 70 °C142 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.33 W
3VA1216-6GF42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1216-6GF42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1216-6GF42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1216-6GF42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1216-6GF42-0AA0 — Mechanical
ParameterValue
Height158 mm
Width140 mm
Depth70 mm
Height (in)6.22 in
Width (in)5.51 in
Depth (in)2.76 in

Product details

SENTRON 3VA1 MCCB — 160 A, 4-Pole, TM240 Release

The 3VA1216-6GF42-0AA0: Interrupting capacity varies sharply with system voltage: 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V. At 240 V the 220 kA figure covers virtually any fault a 160 A frame will see — high available fault current is the main reason you spec this breaker over a smaller-frame MCCB. Current-carrying capacity holds flat at 160 A from 40 °C to 50 °C, then derates to 156 A at 55 °C, 151 A at 60 °C, 147 A at 65 °C, and 142 A at 70 °C. In a warm panel — say 50 °C internal ambient — you still get full 160 A; above that the derating curve governs the actual load you can hang on it.

Front IP40 protection; the breaker accepts optional motor drive accessories for remote operation. N-conductor protection is 100% rated — the fourth pole is fully rated, not a switched neutral. Maximum power loss 33 W at rated current.

Frequently asked questions

What is the interrupting rating of 3VA1216-6GF42-0AA0 at 240 V?

220 kA at 240 V. The rating drops to 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V.

What is the continuous current rating and how does it derate with temperature?

Rated 160 A continuous (Iu). It holds 160 A from 40 °C to 50 °C, then derates to 156 A at 55 °C, 151 A at 60 °C, 147 A at 65 °C, and 142 A at 70 °C.

Where can I buy 3VA1216-6GF42-0AA0?

Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your quantity and target delivery.

MPN
3VA1216-6GF42-0AA0