It is configured as a line protection device — meaning it is set up for feeder and distribution duty, not motor branch-circuit protection. The 200 A rating holds flat from 40 °C up to 50 °C, then derates linearly to 176 A at 70 °C, which matters if this breaker lands in a warm enclosure or near other heat sources in the mill. Breaking capacity is 121 kA at 240 V AC, 75.6 kA at 415 V, 25 kA at 440 V, and 11.9 kA at 690 V.
Dimensions are 105 mm wide, 158 mm high, and 70 mm deep — a standard 3-pole MCCB footprint for the SENTRON 3VA platform. It ships with two auxiliary switches (HP type) installed, which can be wired into a PLC or annunciator for breaker status without needing a separate contact block.