Skip to main content
Siemens 3VA1220-4EF32-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-4EF32-0AE0 SENTRON MCCB, 200 A, 3-Pole, 121

MPN3VA1220-4EF32-0AE0

Siemens SENTRON 3VA1220-4EF32-0AE0, molded case circuit breaker, 3-pole, 200 A rated at 40 °C, TM240 thermal-magnetic release, 121 kA breaking capacity at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1220-4EF32-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12204EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1220-4EF32-0AE0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.42 W
3VA1220-4EF32-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1220-4EF32-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1220-4EF32-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts4
3VA1220-4EF32-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1220-4EF32-0AE0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width105 mm
Depth70 mm
Height (in)6.22 in
Width (in)4.13 in
Depth (in)2.76 in

Product details

The Siemens 3VA1220-4EF32-0AE0 is a SENTRON molded case circuit breaker (MCCB) built for line protection — 3-pole, 200 A continuous at 40 °C, with a TM240 thermal-magnetic trip unit. That 200 A holds steady up to 50 °C; above that it derates to 194 A at 55 °C and 176 A at 70 °C, so if your panel runs hot, you size on the derated number, not the nameplate. Breaking capacity is 121 kA at 240 V AC, dropping to 75.6 kA at 415 V and 52.5 kA at 440 V — enough headroom for most industrial service-entrance or feeder applications where high fault current is a concern.

Sizing and selectivity notes

Power loss maxes at 42 W. No ground-fault monitoring version is included on this variant — that's a separate order code if you need GF protection.

Physical fit in the enclosure

That covers unheated warehouses and outdoor cabinets in most climates.

MPN
3VA1220-4EF32-0AE0