MCCB for line protection — 200 A, 3-pole, TM240 release
Rated 200 A at 40 °C, it holds that full rating through 50 °C, then derates linearly to 176 A at 70 °C — useful for high-ambient panels or tight enclosures where heat buildup is a concern. Interrupting capacity is 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, 17 kA at 500 V, and 11.9 kA at 690 V — figures that cover most industrial distribution panels up to 690 V line-to-line. An undervoltage release (UVR) is fitted as standard.
Dimensions: 105 mm wide, 158 mm high, 70 mm deep. Fits standard Siemens SENTRON mounting base or DIN-rail adapter. The 3-pole footprint is the same across the 3VA1 frame; if you're swapping a 3VA1 160 A frame, check the depth — this unit is 70 mm, matching the frame depth for the 200 A rating.