Skip to main content
Siemens 3VA1220-4EF32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-4EF32-0BH0 SENTRON MCCB, 200 A, 3-Pole, 121

MPN3VA1220-4EF32-0BH0

Siemens SENTRON 3VA1220-4EF32-0BH0, molded case circuit breaker, 3-pole, 200 A, TM240 release, 121 kA at 240 V, 70 mm depth.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1220-4EF32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1220-4EF32-0BH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V25 kA
Breaking capacity at 690 V11.9 kA
3VA1220-4EF32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1220-4EF32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1220-4EF32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1220-4EF32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1220-4EF32-0BH0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1220-4EF32-0BH0 is a 3-pole molded case circuit breaker rated for 200 A continuous current at 40 °C, with a TM240 thermal-magnetic release. It holds the same 200 A rating through 50 °C, then derates to 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C — so in a warm panel you lose about 12 % of capacity at the top of the operating range. Interrupting capacity runs 121 kA at 240 V, 75.6 kA at 415 V, 25 kA at 440 V, and 11.9 kA at 690 V, which covers most industrial distribution fault levels without cascading upstream. Front-side IP40 keeps dust out of the mechanism; the enclosure is sized at 105 mm wide × 158 mm high × 70 mm deep — a standard MCCB footprint for a 200 A frame.

The TM240 release is factory-set and non-interchangeable in the field — verify your cable sizing and coordination study against the 200 A continuous rating before committing the BOM. Undervoltage release coil wiring shares the same terminal compartment as the auxiliary contacts; keep the free-wheel diode polarity correct if the UVR is driven by a DC control supply. The trip indicator on the front face gives a visual flag after a fault event, which saves a multimeter walk during troubleshooting.

Frequently asked questions

What are the key ratings for 3VA1220-4EF32-0BH0?

Rated continuous current Iu is 200 A, interrupting capacity is 121 kA at 240 V, 75.6 kA at 415 V, 25 kA at 440 V, and 11.9 kA at 690 V. It is a 3-pole MCCB with a TM240 thermal-magnetic release and an undervoltage release.

Where can I buy 3VA1220-4EF32-0BH0?

This part is sourced to order through independent distribution channels. Submit an RFQ for current pricing and availability — confirmed at quote time.

What is the depth of 3VA1220-4EF32-0BH0?

The depth is listed as 70 mm.

What is the width of 3VA1220-4EF32-0BH0?

The width is listed as 105 mm.

MPN