Specifications

3VA1220-4EF32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1220-4EF32-0CA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V25 kA
Breaking capacity at 690 V11.9 kA
3VA1220-4EF32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1220-4EF32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1220-4EF32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1220-4EF32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1220-4EF32-0CA0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

The Siemens 3VA1220-4EF32-0CA0 is a 3-pole SENTRON molded case circuit breaker rated for 200 A continuous current (Iu) at 40 °C, with an 800 V insulation voltage (Ui). The interrupting ratings climb to 121 kA at 240 V, 75.6 kA at 415 V, 25 kA at 440 V, and 11.9 kA at 690 V, so it handles high-fault utility feeds and transformer secondaries without cascading upstream.

Above that it derates: 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, 176 A at 70 °C.

The undervoltage release is a factory-integrated option (order code suffix indicates the UVR is built in, not a field-addon kit). No official successor or phase-out notice is on record.

The 105 mm width occupies three 35 mm module spaces; the 70 mm depth leaves room for rear busbar connections in a typical 200 mm deep enclosure. The front IP40 rating means it is not suitable for washdown areas — keep it inside a sealed cabinet. The TM240 release is fixed-trip (thermal-magnetic, not electronic), so coordination studies rely on the published time-current curve for the 3VA platform.

Frequently asked questions

Does 3VA1220-4EF32-0CA0 include an undervoltage release?

Yes, it is factory-equipped with an undervoltage release (UVR) as the auxiliary release type.

What is the depth of 3VA1220-4EF32-0CA0?

The depth is 70 mm, width 105 mm, height 158 mm.

MPN
3VA1220-4EF32-0CA0