Siemens 3VA1220-4EF32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-4EF32-0DA0 SENTRON MCCB, 200 A, 3-Pole, Line

MPN3VA1220-4EF32-0DA0

Siemens SENTRON 3VA1220-4EF32-0DA0, molded case circuit breaker, 3-pole, 200 A rated current, line protection, TM240 release, undervoltage release, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1220-4EF32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1220-4EF32-0DA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V25 kA
Breaking capacity at 690 V11.9 kA
3VA1220-4EF32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1220-4EF32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1220-4EF32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1220-4EF32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1220-4EF32-0DA0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1220-4EF32-0DA0 is a 3-pole molded case circuit breaker (MCCB) rated for 200 A continuous current at 40 °C, with a TM240 thermal-magnetic overcurrent release. It's configured for line protection — no ground fault monitoring, no communication module, no auxiliary contacts.

Breaking capacity and derating

Breaking capacity varies sharply with system voltage: 121 kA at 240 V, 75.6 kA at 415 V, 25 kA at 440 V, and 11.9 kA at 690 V. Current derating starts at 55 °C: full 200 A up to 50 °C, then 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C.

Integration notes

Footprint is 105 mm wide by 158 mm high by 70 mm deep — standard panel-mount dimensions for a 200 A frame MCCB. The integrated undervoltage release (UVR) is fitted as standard; the auxiliary trip module is ordered separately as 3VA9608-0BB25. No auxiliary contact block is included, so if you need status feedback, plan for an add-on.

Frequently asked questions

What is the breaking capacity of this MCCB at 415 V?

At 415 V the breaking capacity is 75.6 kA. At 240 V it's 121 kA, at 440 V it's 25 kA, and at 690 V it's 11.9 kA.

Where can I buy 3VA1220-4EF32-0DA0 and how is it quoted?

This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — both are confirmed at quote time.

MPN