Skip to main content
Siemens 3VA1220-4EF32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-4EF32-0HA0 SENTRON MCCB, 200 A, 3-Pole, Line

MPN3VA1220-4EF32-0HA0

Siemens SENTRON 3VA1220-4EF32-0HA0, molded case circuit breaker, 3-pole, 200 A rated continuous current, line protection, with shunt trip (STL), breaking capacity 121 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1220-4EF32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1220-4EF32-0HA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V25 kA
Breaking capacity at 690 V11.9 kA
3VA1220-4EF32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1220-4EF32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1220-4EF32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1220-4EF32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1220-4EF32-0HA0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

The Siemens 3VA1220-4EF32-0HA0 is a SENTRON molded case circuit breaker (MCCB) rated for 200 A continuous current at 40 °C, with a 3-pole configuration and a TM240 thermal-magnetic overcurrent release. It is built for line protection — meaning it sits on the feeder side of a distribution panel to protect cables and busbars from overloads and short circuits.

This MCCB delivers 121 kA at 240 V, 75.6 kA at 415 V, 25 kA at 440 V, and 11.9 kA at 690 V. For a 415 V distribution board with a prospective short-circuit current of, say, 50 kA, this breaker gives you 25 kA of headroom — that is selectivity margin for the upstream transformer.

Thermal derating — the real-world current you can pull

Above that, it derates: 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C. If your panel ambient runs at 60 °C, you lose 12 A from the nameplate rating — plan your load accordingly.

It is a fixed (non-plug-in) MCCB designed for screw-mounting onto a mounting plate or into a distribution panel. No auxiliary contacts are fitted as standard; if you need status feedback, you will add them separately.

Frequently asked questions

Who supplies 3VA1220-4EF32-0HA0 and how is it quoted for volume purchases?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of this MCCB at 415 V?

At 415 V the breaking capacity is 75.6 kA.

Does this breaker include a shunt trip?

Yes, it is fitted with a shunt trip (STL) auxiliary release, order code 3VA9688-0BL30, for remote tripping.

What is the rated continuous current at 60 °C?

At 60 °C the rated continuous current derates to 188 A.

MPN
3VA1220-4EF32-0HA0