Skip to main content
Siemens 3VA1220-4EF42-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-4EF42-0BC0 SENTRON MCCB, 200 A, 4P, 121 kA a

MPN3VA1220-4EF42-0BC0

Siemens SENTRON 3VA1220-4EF42-0BC0 molded case circuit breaker, 200 A rated continuous current, 4-pole, line protection version, TM240 thermal-magnetic release, 121 kA breaking capacity at 240 V, IP40 front protection, with undervoltage release and 2 HQ auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1220-4EF42-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1220-4EF42-0BC0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V25 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1220-4EF42-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1220-4EF42-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1220-4EF42-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1220-4EF42-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1220-4EF42-0BC0 — Mechanical
ParameterValue
Height158 mm
Width140 mm
Depth70 mm

Product details

What the ratings mean for your panel

The 3VA1220-4EF42-0BC0 is a SENTRON molded case circuit breaker rated for 200 A continuous current (Iu) across ambient temperatures up to 50 °C — at 55 °C it derates to 194 A, at 70 °C to 176 A, so the full 200 A is available in most ventilated enclosures. The 4-pole construction with TM240 thermal-magnetic overcurrent release handles line protection (not feeder or motor protection; no phase-failure detection, no ground-fault monitoring). Breaking capacity is 121 kA at 240 V, 75.6 kA at 415 V, and 25 kA at 440 V — enough for high-fault utility feeds or transformer secondaries. The integrated undervoltage release (UVR) and two HQ auxiliary switches (order code 3VA9608-0BB11 for the trip unit) are built in, so no separate add-on modules are needed for those functions.

Panel integration notes

Dimensions are 140 mm wide, 158 mm high, 70 mm deep — fits standard MCCB mounting footprints in distribution boards and control panels. Front IP40 protection means it is suitable for dry indoor enclosures; no washdown rating. The 2 HQ auxiliary switches provide status feedback for PLC or SCADA inputs. The undervoltage release trips the breaker when supply drops below a threshold, preventing automatic restart after a brownout — useful for conveyor or pump circuits where uncontrolled restart is a safety concern.

Comparison with 3VA1010-2ED32-0JA0

The 3VA1010-2ED32-0JA0 is a lower-rated sibling in the same SENTRON 3VA family — typically 100 A frame versus this 200 A frame. The 3VA1220-4EF42-0BC0 carries higher interrupting capacity at every voltage point and includes the undervoltage release as standard; the 3VA1010-2ED32-0JA0 may omit the UVR and have fewer auxiliary contacts. Physically, the 3VA1220-4EF42-0BC0 is wider (140 mm vs. the 100 A frame's 105 mm) so a panel cutout for the smaller breaker will need modification to accept this one. If the BOM specifies the 3VA1010-2ED32-0JA0, this 200 A unit will not drop in without rewiring and re-cutting the mounting plate.

Frequently asked questions

How do I get current pricing and availability for 3VA1220-4EF42-0BC0?

Submit an RFQ through this listing; pricing and stock are confirmed at quote time through independent distribution channels.

Will 3VA1220-4EF42-0BC0 drop into a panel specified around 3VA1010-2ED32-0JA0 without rewiring?

No — the 3VA1220-4EF42-0BC0 is 140 mm wide versus the 100 A frame's 105 mm, so the mounting cutout and bus connections will need modification.

What is the breaking capacity of 3VA1220-4EF42-0BC0 at 415 V?

It is rated 75.6 kA at 415 V, with 121 kA at 240 V and 25 kA at 440 V.

MPN
3VA1220-4EF42-0BC0