Siemens 3VA1220-4EF42-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-4EF42-0CH0 SENTRON MCCB, 200 A, 4-Pole, 70 m

MPN3VA1220-4EF42-0CH0

Siemens SENTRON 3VA1220-4EF42-0CH0, molded case circuit breaker, 4-pole, 200 A rated current, 121 kA breaking capacity at 240 V, line protection design with undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1220-4EF42-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12204EF420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1220-4EF42-0CH0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.44.5 W
3VA1220-4EF42-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1220-4EF42-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1220-4EF42-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1220-4EF42-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1220-4EF42-0CH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width140 mm
Depth70 mm
Height (in)6.22 in
Width (in)5.51 in
Depth (in)2.76 in

Product details

The 3VA1220-4EF42-0CH0: Rated current holds at 200 A from 40 °C through 50 °C, then derates linearly to 176 A at 70 °C. That thermal curve means the breaker can be loaded to nameplate in most ventilated enclosures; only tight-gland or high-ambient panels need the derated figure. Breaking capacity steps down with system voltage: 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, 17 kA at 500 V, and 11.9 kA at 690 V. For a 480 V panel (common in North American industrial) the 52.5 kA at 440 V is the closest published figure — still well above typical 25–35 kA available fault currents. No ground-fault monitoring or communication module on this build.

Frequently asked questions

Where can I buy 3VA1220-4EF42-0CH0?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is the breaking capacity of 3VA1220-4EF42-0CH0?

121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, 17 kA at 500 V, and 11.9 kA at 690 V.

Does 3VA1220-4EF42-0CH0 include an undervoltage release?

Yes, it includes an undervoltage release (UVR) plus 2 auxiliary switches and 1 trip alarm switch (HQ type).

MPN
3VA1220-4EF42-0CH0