MCCB with 200 A continuous rating and high interrupting capacity
Its interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V, 36 kA at 440 V, and 17 kA at 690 V — figures that cover most industrial fault-current scenarios without needing an upstream current-limiting fuse.
Current derating and ambient temperature
Above that, derating is gradual: 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C. In a warm panel — say 55 °C internal ambient — you lose only 6 A, so the 200 A frame still comfortably protects a 190 A continuous load.
Dimensions: 105 mm wide, 158 mm high, 70 mm deep. The 105 mm width is the standard 3-pole MCCB footprint for the SENTRON 3VA platform — fits the same panel cutout and bus-bar spacing as the 3VA1112-5EF32-0CA0 and other 3-pole 3VA frames. Front IP40 protection; no auxiliary contact slot populated, so if you need a status signal you'll add the 3VA9608-0BB25 auxiliary trip accessory.