Skip to main content
Siemens 3VA1220-5EF32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-5EF32-0JC0 SENTRON MCCB, 200 A, 3-Pole, Line

MPN3VA1220-5EF32-0JC0

Siemens SENTRON, molded case circuit breaker, 3VA1220-5EF32-0JC0, 200 A, 3-pole, line protection, 187 kA at 240 V, TM240 release, shunt trip, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1220-5EF32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1220-5EF32-0JC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V36 kA
Breaking capacity at 690 V17 kA
3VA1220-5EF32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1220-5EF32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1220-5EF32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1220-5EF32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1220-5EF32-0JC0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

Its TM240 thermal-magnetic release handles overloads and short circuits, while the integrated shunt trip (STL) allows remote tripping via a separate control signal. Breaking capacity reaches 187 kA at 240 V AC, 121 kA at 415 V, and 36 kA at 440 V — enough for high-fault industrial distribution panels where upstream transformer capacity is large.

The 200 A rating holds flat from 40 °C to 50 °C, then derates to 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C.

The shunt trip (STL) requires a separate control voltage; the auxiliary release order code is 3VA9688-0BL32 if you need a spare or replacement coil assembly.

Frequently asked questions

How do I get current pricing and availability for 3VA1220-5EF32-0JC0?

Submit an RFQ through this listing. We source this part through independent distribution and provide a firm quote with confirmed lead time at the time of request.

What is the breaking capacity of 3VA1220-5EF32-0JC0 at 415 V?

121 kA at 415 V AC. At 240 V it is 187 kA, at 440 V it is 36 kA, and at 690 V it is 17 kA.

Will 3VA1220-5EF32-0JC0 fit in a panel designed for 3VA1110-5EE32-0JA0?

The 3VA1220-5EF32-0JC0 is a 200 A frame, physically larger than the 3VA1110-5EE32-0JA0 (which is a 100 A class). The 105 mm width and 158 mm height are bigger, so it will not drop into the same cutout or DIN-rail footprint without panel modification.

MPN
3VA1220-5EF32-0JC0