Its interrupting capacity reaches 187 kA at 240 V AC, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V — meaning it can safely clear faults up to those levels without cascading upstream.
Rated current holds at 200 A from 40 °C through 50 °C ambient, then derates to 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C. Maximum power loss is 42 W. For a panel builder, that means the breaker can be grouped in a 50 °C enclosure without current reduction — above that, the derating curve governs the actual load it can carry.
It does not include an undervoltage release or ground-fault monitoring.