Skip to main content
Siemens 3VA1220-5GF42-0AB0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-5GF42-0AB0 SENTRON MCCB, 200 A, 4-Pole, 187

MPN3VA1220-5GF42-0AB0

Siemens SENTRON 3VA1220-5GF42-0AB0, molded case circuit breaker, 4-pole, 200 A, TM240 release, line protection, 70 mm depth, 140 mm width, 158 mm height.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1220-5GF42-0AB0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12205GF420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA11
3VA1220-5GF42-0AB0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.42 W
3VA1220-5GF42-0AB0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1220-5GF42-0AB0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1220-5GF42-0AB0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1220-5GF42-0AB0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1220-5GF42-0AB0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width140 mm
Depth70 mm
Height (in)6.22 in
Width (in)5.51 in
Depth (in)2.76 in

Product details

Line protection breaker, 200 A continuous, 187 kA interrupting at 240 V

Its interrupting capacity scales with system voltage: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V (–). The 200 A rating holds flat from 40 °C to 50 °C, then derates to 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C (–). For a panel that runs warm — say 55 °C ambient — you have 194 A of headroom; above that, the breaker still delivers but you lose 6 A per 5 °C step. Rated insulation voltage is 800 V, with an operating range of -25 °C to 70 °C and storage from -40 °C to 80 °C. Full-load power dissipation is 42 W max.

DIN-rail footprint and auxiliary switch complement

Two factory-fitted auxiliary switches (HP type) are supplied with the basic switch; no additional trip indicator or voltage trigger is included. Communication-function option is absent on this variant.

Frequently asked questions

Where can I buy 3VA1220-5GF42-0AB0 and how do I get a price?

This breaker is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to receive current pricing and availability confirmation.

What interrupting capacity does 3VA1220-5GF42-0AB0 have at common voltages?

At 240 V the interrupting rating is 187 kA; at 415 V it is 121 kA; at 440 V, 75.6 kA; at 500 V, 30 kA; and at 690 V, 17 kA (–). These values assume the rated 200 A continuous current.

What is the depth of 3VA1220-5GF42-0AB0?

The depth is 70 mm (2.76 in).

MPN
3VA1220-5GF42-0AB0