200 A MCCB with voltage-dependent SCCR curve
The Siemens SENTRON 3VA1220-5GF42-0JH0 is a 4-pole molded case circuit breaker rated for 200 A continuous at 40 °C, with no derating needed up to 50 °C — it holds 200 A flat through that range, then steps down to 176 A at 70 °C. The interrupting capacity follows the system voltage: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V.
Line protection with auxiliary switching and shunt trip
The 70 mm depth and 140 mm width fit standard SENTRON panel footprints — drop it into a 4-pole MCCB slot without reworking the busbar arrangement.