Skip to main content
Siemens 3VA1220-5MH32-0CH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-5MH32-0CH0 SENTRON MCCB, 200 A, 3-Pole, Star

MPN3VA1220-5MH32-0CH0

Siemens SENTRON molded case circuit breaker, 3VA1220-5MH32-0CH0, 3-pole, 200 A rated continuous current, starter protection version with TM120M overcurrent release, 187 kA interrupting at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1220-5MH32-0CH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionStarter protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1220-5MH32-0CH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C192 A
Current at 60 °C188 A
Current at 65 °C184 A
Current at 70 °C180 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V30 kA
Breaking capacity at 690 V17 kA
3VA1220-5MH32-0CH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM120M
3VA1220-5MH32-0CH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1220-5MH32-0CH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1220-5MH32-0CH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1220-5MH32-0CH0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

Interrupting ratings and thermal derating

The 3VA1220-5MH32-0CH0: The 187 kA at 240 V and 121 kA at 415 V mean this breaker can be applied on high-capacity transformers or busway taps where fault current is severe. At 440 V it still clears 30 kA, and at 690 V it holds 17 kA — so it's usable on 480/277 V and 600 V industrial systems, though the lower 690 V rating means you check the available fault current at that voltage. Rated continuous current is 200 A from 40 °C through 50 °C ambient; it derates to 192 A at 55 °C, 188 A at 60 °C, 184 A at 65 °C, and 180 A at 70 °C.

Starter protection and auxiliary configuration

This is the starter protection version (product version field), meaning the TM120M release is coordinated for motor starting inrush — it won't nuisance-trip on the locked-rotor current of a typical induction motor.

That 105 mm width is a standard 4-module footprint for SENTRON 3VA MCCBs — it fits the same panel cutout and bus-bar spacing as other 3VA 3-pole frames.

Frequently asked questions

How do I get current pricing and availability for 3VA1220-5MH32-0CH0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the interrupting capacity of this MCCB at 240 V and 415 V?

It interrupts 187 kA at 240 V and 121 kA at 415 V, making it suitable for high-fault-current applications like transformer secondaries or busway taps.

Does 3VA1220-5MH32-0CH0 include an undervoltage release?

Yes, it includes an undervoltage release (UVR) that drops the load on loss of control voltage, plus 2 auxiliary switches and 1 trip alarm switch for status feedback.

MPN
3VA1220-5MH32-0CH0