Skip to main content
Siemens 3VA1220-6EF32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-6EF32-0AD0 SENTRON MCCB, 200A, 3-Pole, 220kA

MPN3VA1220-6EF32-0AD0

Siemens SENTRON 3VA1220-6EF32-0AD0, molded case circuit breaker, 3-pole, 200 A, TM240 thermal-magnetic release, line protection, 220 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1220-6EF32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12206EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1220-6EF32-0AD0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.42 W
3VA1220-6EF32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1220-6EF32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1220-6EF32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1220-6EF32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1220-6EF32-0AD0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width105 mm
Depth70 mm
Height (in)6.22 in
Width (in)4.13 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1220-6EF32-0AD0 is a 3-pole molded case circuit breaker rated 200 A continuous at 40–50 °C, with a TM240 thermal-magnetic release and a line-protection design. It is built for main feeder or large branch-circuit duty in distribution panels, switchboards, and industrial enclosures — the class of part that sits between the transformer secondary and the downstream load centers.

This breaker carries 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V. For a 480 V panel in North America, the relevant figure is the 440 V rating (75.6 kA), which covers the typical 480Y/277 V service. At 690 V, the 17 kA Icu still clears most industrial fault levels, but if your transformer is large enough to push 25 kA at 690 V, you need a higher-rated frame. The thermal derating curve is flat from 40 °C to 50 °C at 200 A (–), then drops to 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C. If your panel ambient hits 55 °C, you lose 6 A — plan the load accordingly. Power loss at full rating is 42 W maximum, which matters for heat buildup in a sealed enclosure.

Frequently asked questions

Where can I buy 3VA1220-6EF32-0AD0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — no stock count or price can be stated here, but the supply channel is open.

What is the breaking capacity of 3VA1220-6EF32-0AD0 at different voltages?

220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V. These are the ultimate short-circuit breaking capacities (Icu) at each voltage level.

Will 3VA1220-6EF32-0AD0 drop into a panel specified around 3VA1112-5EE32-0AA0 without rewiring?

The 105 mm width and 158 mm height match the standard 3VA 3-pole footprint, so a panel drilled for a 3VA1112 frame will accept this breaker without mechanical rework. However, the 200 A rating versus the lower-rated 3VA1112 means the incoming cable and bus must be sized for 200 A — verify conductor ampacity before swapping.

MPN
3VA1220-6EF32-0AD0