That 200 A holds flat through 50 °C — at 55 °C it begins to taper to 194 A, dropping to 176 A at 70 °C, which matters if this breaker lives in a hot panel near other heat sources. Short-circuit interrupting capacity is the headline here: 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V. The shunt trip lets a remote signal — from an E-stop, a fire alarm relay, or a PLC digital output — force the breaker open. The auxiliary switches report the contact position back to the control system or status panel.
Dimensions: 105 mm wide, 158 mm tall, 70 mm deep. The 70 mm depth leaves room for rear-access bus connections and wiring trough clearance.
Power dissipation at full load is 42 W maximum — that's the heat the panel's ventilation or air conditioning must handle per breaker.