Breaking capacity runs 220 kA at 240 VAC, 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V — so it handles high-fault utility feeds and transformer secondaries without cascading upstream. The 70 mm depth × 105 mm width × 158 mm height footprint fits standard Siemens SENTRON mounting bases; no adapter plate needed for a 3-pole frame.
Above that, it derates: 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C.
Integrated accessories — shunt trip and aux switches