Skip to main content
Siemens 3VA1220-6EF32-0KA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-6EF32-0KA0 SENTRON MCCB, 200 A, 220 kA

MPN3VA1220-6EF32-0KA0

Siemens SENTRON 3VA1220-6EF32-0KA0, molded case circuit breaker, 3-pole, 200 A, TM240 release, shunt trip, 220 kA at 240 V, 154 kA at 415 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1220-6EF32-0KA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1220-6EF32-0KA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V36 kA
Breaking capacity at 690 V17 kA
3VA1220-6EF32-0KA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1220-6EF32-0KA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1220-6EF32-0KA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1220-6EF32-0KA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1220-6EF32-0KA0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

MCCB for high-fault panels

Above that, derate linearly: 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, 176 A at 70 °C. If the panel interior runs hot — say, adjacent to a drive or transformer — factor the 55 °C or 60 °C row into your continuous-load calculation. Footprint: 105 mm wide, 158 mm tall, 70 mm deep. Standard DIN-rail or screw-mount panel integration. The 15 000 mechanical-endurance cycles suit switching applications where the breaker sees regular operation, not just fault protection.

Frequently asked questions

Does this MCCB include an undervoltage release or ground-fault monitoring?

No. It has a shunt trip (STL) only. No undervoltage release, no ground-fault monitoring, no communication module. It is a straight line-protection breaker with remote-trip via the shunt coil.

MPN
3VA1220-6EF32-0KA0