The interrupting ratings tell you where it can clear a fault without welding or bursting: 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V — so it handles high available fault current on the secondary side of a large transformer or in a heavy industrial feeder. This breaker carries a shunt trip release (STL) and two factory-fitted auxiliary switches (HQ) — so it can be remotely tripped by a safety circuit or PLC and gives status feedback.

Siemens 3VA1220-6EF32-0KC0 SENTRON MCCB, 200 A, 3-Pole, 220
Siemens SENTRON 3VA1220-6EF32-0KC0, molded case circuit breaker, 3-pole, 200 A, interrupting rating 220 kA at 240 V AC, line protection, shunt trip release, 2 auxiliary switches HQ.
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Basic switch (supplied) ref. | 3VA12206EF320AA0 |
| Integrated auxiliary / alarm switch ref. | 3VA9988-0AA12 |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 200 A |
| Current at 45 °C | 200 A |
| Current at 50 °C | 200 A |
| Current at 55 °C | 194 A |
| Current at 60 °C | 188 A |
| Current at 65 °C | 182 A |
| Current at 70 °C | 176 A |
| Switching capacity class | H |
| Breaking capacity at 240 V | 220 kA |
| Breaking capacity at 415 V | 154 kA |
| Breaking capacity at 440 V | 75.6 kA |
| Breaking capacity at 500 V | 30 kA |
| Breaking capacity at 690 V | 17 kA |
| Power loss, max. | 42 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM240 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | nut keeper kit on both ends |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | Yes |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 2 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 20 000 |
| Height | 158 mm |
| Width | 105 mm |
| Depth | 70 mm |
| Height (in) | 6.22 in |
| Width (in) | 4.13 in |
| Depth (in) | 2.76 in |
Product details
Frequently asked questions
Where can I buy 3VA1220-6EF32-0KC0?
This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.
What is the interrupting rating of 3VA1220-6EF32-0KC0 at 415 V?
154 kA at 415 V.