Siemens 3VA1220-6EF42-0AC0 SENTRON MCCB, 200 A, 4-Pole, 220

MPN3VA1220-6EF42-0AC0

Siemens SENTRON 3VA1220-6EF42-0AC0, molded case circuit breaker, 4-pole, TM240 thermal-magnetic release, 200 A at 40 °C, 220 kA interrupting at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1220-6EF42-0AC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12206EF420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1220-6EF42-0AC0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.42 W
3VA1220-6EF42-0AC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1220-6EF42-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1220-6EF42-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1220-6EF42-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1220-6EF42-0AC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width140 mm
Depth70 mm
Height (in)6.22 in
Width (in)5.51 in
Depth (in)2.76 in

Product details

Its 4-pole design handles three-phase plus neutral switching, common in North American and IEC distribution panels where full isolation is required. Interrupting capacity is the headline here: 220 kA at 240 V AC, 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V. That SCCR ladder means it can sit upstream of a transformer or in a high-fault industrial service entrance without cascading failure — the breaker clears before the fault energy damages downstream gear. Power loss maxes at 42 W — relevant for enclosed panel thermal calculations, especially when grouping multiple breakers.

Thermal derating and ambient

Above that it derates: 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, 176 A at 70 °C.

Auxiliary switching and options

The basic switch order code is 3VA12206EF420AA0 if you need to reference the switching mechanism separately.

Frequently asked questions

Where can I buy 3VA1220-6EF42-0AC0 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the interrupting capacity of 3VA1220-6EF42-0AC0 at 240 V?

220 kA at 240 V AC — sufficient for high-fault service-entrance or transformer-secondary applications where available fault current exceeds typical 65 kA or 100 kA MCCB ratings.

What does the TM240 release designation mean?

TM240 is a thermal-magnetic overcurrent release rated 200 A continuous at 40 °C. The '240' refers to the release frame size; actual trip settings are fixed within the breaker, not adjustable.

Will 3VA1220-6EF42-0AC0 drop into a panel specified around 3VA1110-5ED36-0AC0 without rewiring?

Both are 4-pole SENTRON 3VA breakers with the same 70 mm depth and 158 mm height, so the mounting footprint and bus-bar centers match. Width differs — 140 mm on this 200 A frame versus the narrower 3VA1110 frame — so check bus-bar span and adjacent device spacing before swapping.