Skip to main content
Siemens 3VA1220-6EF42-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-6EF42-0AH0 SENTRON MCCB, 200A, 220kA at 240V

MPN3VA1220-6EF42-0AH0

Siemens SENTRON 3VA1220-6EF42-0AH0, molded case circuit breaker, 4-pole, 200 A at 40 °C, breaking capacity 220 kA at 240 V, TM240 thermal-magnetic release, line protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1220-6EF42-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12206EF420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1220-6EF42-0AH0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.42 W

Protection & Trip Unit

3VA1220-6EF42-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1220-6EF42-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1220-6EF42-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1220-6EF42-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1220-6EF42-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width140 mm
Depth70 mm
Height (in)6.22 in
Width (in)5.51 in
Depth (in)2.76 in

Product details

What this MCCB delivers on a distribution bus

The Siemens 3VA1220-6EF42-0AH0 is a 4-pole SENTRON molded case circuit breaker designed for line protection, with a continuous current rating of 200 A at 40 °C and a thermal-magnetic TM240 release. Its headline breaking capacity hits 220 kA at 240 V, stepping down to 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V — so it handles high-fault utility feeds or transformer secondaries where upstream SCCR demands serious interrupting muscle. The 800 V rated insulation voltage confirms it's built for 690 V industrial networks with margin.

Thermal derating and real-world current

Rated 200 A at 40 °C, the 3VA1220-6EF42-0AH0 holds that same 200 A through 45 °C and 50 °C. At 55 °C it derates to 194 A, then 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C. In a warm panel — say 55 °C ambient — you lose only 6 A, so this breaker fits tightly packed switchboards without oversizing.

Physical fit and auxiliary switching

Dimensions: 158 mm high, 140 mm wide, 70 mm deep. The 4-pole body fits standard SENTRON mounting footprints. It ships with 2 auxiliary switches plus 1 trip alarm switch HQ, giving remote status and trip indication without an add-on module. The supplied basic switch variant is 3VA12206EF420AA0, which means the internal switching mechanism is pre-configured for this order code.

Frequently asked questions

What is the breaking capacity of this MCCB at different voltages?

At 240 V it interrupts 220 kA, at 415 V it interrupts 154 kA, at 440 V it interrupts 75.6 kA, at 500 V it interrupts 30 kA, and at 690 V it interrupts 17 kA.

Where can I buy 3VA1220-6EF42-0AH0?

Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
3VA1220-6EF42-0AH0