Skip to main content
Siemens 3VA1220-6EF42-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-6EF42-0CC0 SENTRON MCCB, 200 A, 4-Pole, Line

MPN3VA1220-6EF42-0CC0

Siemens SENTRON 3VA1220-6EF42-0CC0, Molded case circuit breaker, 4-pole, 200 A rated continuous current Iu, TM240 overcurrent release, Line protection version, with undervoltage release and 2 auxiliary switches HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1220-6EF42-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1220-6EF42-0CC0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V36 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1220-6EF42-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1220-6EF42-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1220-6EF42-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1220-6EF42-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1220-6EF42-0CC0 — Mechanical
ParameterValue
Height158 mm
Width140 mm
Depth70 mm

Product details

Rated for 200 A continuous, 4-pole — what that means in the panel

The Siemens SENTRON 3VA1220-6EF42-0CC0 is a 4-pole molded case circuit breaker (MCCB) rated for 200 A continuous current (Iu) across the full ambient range up to 50 °C, with thermal derating starting at 55 °C (194 A) down to 176 A at 70 °C. That 200 A rating holds steady at 40 °C, 45 °C, and 50 °C — so in a typical 40 °C panel you get the full nameplate without derating. The TM240 overcurrent release is a thermal-magnetic unit — thermal for overload protection, magnetic for short-circuit. It's fixed-trip, not adjustable, so what you order is what coordinates with downstream feeders. The breaker is designated for line protection, meaning it's the main incoming device, not a feeder or branch protector.

Breaking capacity — the real selectivity number

Rated breaking capacity varies sharply with system voltage: 220 kA at 240 V, 154 kA at 415 V, 36 kA at 440 V, and 17 kA at 690 V. At 415 V — common in industrial distribution — you're looking at 154 kA, which is high enough for most main service entrances without cascading upstream. The 36 kA at 440 V is still robust for secondary distribution. If your system runs at 690 V, the 17 kA rating is the binding constraint for fault current coordination studies.

Built-in undervoltage release and auxiliary contacts

This variant comes factory-fitted with an undervoltage release (UVR) — part of the auxiliary release design — and 2 auxiliary switches (HQ type). The UVR trips the breaker when control voltage drops below a threshold, which is standard for emergency-stop circuits or undervoltage protection on motor feeders. The two auxiliary switches provide status feedback (open/closed) to a PLC or indication lamp without needing an external contact block. The integrated auxiliary trip is specified as order code 3VA9608-0BB24 — that's the factory-installed shunt or UVR module, not a field-addable kit. Verify your panel wiring accommodates the UVR coil power requirements before commissioning.

Physical fit and panel integration

Dimensions: 140 mm wide, 158 mm high, 70 mm deep. That's a standard 4-pole MCCB footprint for the 3VA frame size — mounts on a DIN rail or panel-mount plate. The front face carries IP40 protection, meaning it's protected against tools and wires >1 mm but not against water ingress; keep it inside a rated enclosure. Storage range is -40 °C to 80 °C; operating range is -25 °C to 70 °C.

Frequently asked questions

Where can I buy 3VA1220-6EF42-0CC0 and how is it quoted?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of 3VA1220-6EF42-0CC0 at 415 V?

At 415 V the rated breaking capacity is 154 kA. At 240 V it is 220 kA, at 440 V it is 36 kA, and at 690 V it is 17 kA.

Does 3VA1220-6EF42-0CC0 have an undervoltage release?

Yes, it is factory-equipped with an undervoltage release (UVR) as part of the auxiliary release design, plus 2 auxiliary switches HQ for status feedback.

MPN
3VA1220-6EF42-0CC0