Circuit breaker for motor starter protection
Rated In=200 A with a TM120M thermal-magnetic trip unit configured for motor starting duty. Note: this variant ships without overload protection — the thermal element is omitted — so it is a magnetic-only breaker for use ahead of a separate overload relay or motor-protective device. The integrated undervoltage release (UVR) operates on 24 V DC.
The lifecycle stage for this order code is listed as current.
Mounts on DIN rail per the 3VA1 family footprint. The nut keeper kit (included in this order code) secures the breaker to the rail for applications subject to vibration. The UVR coil and auxiliary switches terminate via screw terminals; verify free-wheel diode polarity if the control circuit is inductive.