Siemens SENTRON 3VA1220-6MH32-0JC0 — 200 A MCCB with shunt trip
It carries a 220 kA interrupting rating at 240 V AC, stepping down to 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 4.5 kA at 690 V — so the available fault current at the panel dictates which voltage column governs your coordination study. The unit includes a factory-installed shunt trip (STL) and two HQ auxiliary switches, saving a panel-build step versus field-fitting them later.
Rated 200 A continuous at 40 °C through 50 °C ambient; above that the breaker derates linearly to 176 A at 70 °C. Maximum power loss is 42 W per pole — enough heat to factor into enclosure ventilation if you are stacking multiple breakers in a sealed cabinet.
The depth leaves clearance for rear-connected bus bars or a cable entry gland plate.