At 240 V the breaker clears 220 kA; at 415 V it holds 154 kA, at 440 V it drops to 75.6 kA, at 500 V to 30 kA, and at 690 V to 4.5 kA. That steep derating is typical for a compact MCCB — the arc extinction physics scale with voltage.
The shunt trip lets a safety PLC or E-stop circuit drop the breaker independently of the overload curve — useful for emergency-off chains. No undervoltage release fitted, no ground-fault monitoring module.