Skip to main content
Siemens 3VA1225-1AA32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-1AA32-0AA0 Switch Disconnector, 250 A

MPN3VA1225-1AA32-0AA0
Active

Siemens SENTRON 3VA1225-1AA32-0AA0, a 3-pole switch disconnector in MCCB design, rated 250 A at 690 V AC, 70 mm depth.

$792.23Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1225-1AA32-0AA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
3VA1225-1AA32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C243 A
Current at 60 °C237 A
Current at 65 °C230 A
Current at 70 °C223 A
Power loss, max.57 W
3VA1225-1AA32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1225-1AA32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1225-1AA32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1225-1AA32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height158 mm
Width105 mm
Depth70 mm

Product details

What this 3VA1 switch disconnector is for

The Siemens 3VA1225-1AA32-0AA0 is a SENTRON 3VA1 IEC frame 250 switch disconnector — a 3-pole device rated 250 A at 690 V AC (500 V DC) that provides visible isolation for a circuit without overload or short-circuit protection. It is the disconnect-only variant in the 3VA molded-case family, designed for applications where the upstream feeder already provides protection and you need a load-break switch with a clear open position for lockout/tagout.

Above that it steps down: 243 A at 55 °C, 237 A at 60 °C, 230 A at 65 °C, and 223 A at 70 °C.

The main circuit connection is a front-terminal busbar connection, and the device accepts an optional motor drive for remote switching. IP40 protection on the front face suits enclosed panel mounting. The 15 000-cycle typical mechanical service life reflects a switch disconnector duty cycle — no arc-chamber wear from fault interruption.

Frequently asked questions

Can 3VA1225-1AA32-0AA0 be used as a main disconnect switch?

Yes — it is specifically designed as a switch disconnector in MCCB form factor, rated 250 A at 690 V AC, with visible isolation for use as a main disconnect or load-break switch where upstream protection is already in place.

MPN
3VA1225-1AA32-0AA0