Skip to main content
Siemens 3VA1225-1AA32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-1AA32-0JC0 SENTRON Switch Disconnector, 250

MPN3VA1225-1AA32-0JC0

Siemens SENTRON, switch disconnector, 3VA1225-1AA32-0JC0, 3-pole, 250 A, 690 V AC / 500 V DC, shunt trip STL 110-127 V DC/AC, 2 auxiliary switches HQ, busbar connection, front terminal, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1225-1AA32-0JC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1225-1AA32-0JC0 — Ratings
ParameterValue
Number of poles3
Power loss, max.57 W
3VA1225-1AA32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1225-1AA32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1225-1AA32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1225-1AA32-0JC0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1225-1AA32-0JC0 is a 3-pole switch disconnector in the SD100 variant of the 3VA IEC frame, rated for a continuous current Iu of 250 A. It provides visible isolation for a circuit under load — no overcurrent or short-circuit protection built in, so it serves as a main disconnect or maintenance isolation point where the upstream breaker handles fault clearing. The 250 A continuous rating matches a 250 A frame, sized for feeder or large-motor disconnect duty. The unit carries a short-time withstand of 3 kA for 1 s — that's the fault current it must survive closed until the upstream protective device clears. For a switch disconnector, this rating governs the maximum available fault current at its line side.

Auxiliary and trip options — shunt trip and 2 HQ aux switches

The shunt trip is wired separately from the main power path; energizing it trips the mechanism. Two HQ auxiliary switches (form C, 2 CO contacts) provide status feedback — closed/ open position signals back to the control system. The HQ designation indicates a high-qualified switch rated for control-circuit reliability. No undervoltage release is fitted on this order code. If the application requires a UVR (trip on power loss), a different variant or a field-installable accessory is needed. The unit also supports an optional motor drive (product extension optional yes) for remote motorized operation — useful in automated disconnects.

Integration into the panel — dimensions, connection, environment

The 3VA1225-1AA32-0JC0 occupies a 105 mm width, 158 mm height, and 70 mm depth on the panel face — a 3-pole frame that fits standard SENTRON mounting footprints. Main circuit connection is via busbar connection at the front terminal, meaning the line and load conductors land on busbars that bolt to the front of the disconnect. This is typical for main-switch applications where the busbar runs across multiple disconnects or feeds a distribution block. Front protection is IP40. Maximum power loss is 57 W. In a typical line-disconnect role cycled once per shift, this translates to decades of service. For frequent switching under load, consult the electrical endurance curve in the device manual.

Lifecycle and sourcing reality — current production, quoted to order

The part is specified into the BOM as a Siemens SENTRON switch disconnector, and the order code uniquely identifies the shunt-trip voltage and auxiliary switch configuration.

Frequently asked questions

What is the closest functional second-source — 3VA1110-5EE32-0JA0?

The 3VA1110-5EE32-0JA0 is a molded-case circuit breaker (line protection), not a switch disconnector. It carries a 100 A frame with overcurrent release (TM220) and lacks the 250 A continuous rating. It will not drop into the same panel without rewiring — different width (76.2 mm vs 105 mm) and different connection type (lug terminal vs busbar). The correct replacement is the 3VA1225-1AA32-0JC0 itself.

Will 3VA1225-1AA32-0JC0 drop into a panel that was specified around 3VA1110-5EE32-0JA0 without rewiring?

No. The 3VA1225-1AA32-0JC0 is 105 mm wide vs 76.2 mm for the 3VA1110-5EE32-0JA0, and uses busbar connection (front terminal) vs lug terminal. The mounting hole pattern, busbar arrangement, and conductor terminations are different — rewiring and possibly a new mounting plate are required.

MPN
3VA1225-1AA32-0JC0