Skip to main content
Siemens 3VA1225-1AA42-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-1AA42-0BA0 SENTRON Switch Disconnector, 250

MPN3VA1225-1AA42-0BA0

Siemens SENTRON 3VA1225-1AA42-0BA0, switch disconnector in MCCB design, 4-pole, In=250 A, without overload or short-circuit protection, with undervoltage release (UVR) 24 V DC, busbar connection, front terminal.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1225-1AA42-0BA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design

Ratings

3VA1225-1AA42-0BA0 — Ratings
ParameterValue
Number of poles4
Power loss, max.57 W

Construction & Connection

3VA1225-1AA42-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1225-1AA42-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1225-1AA42-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1225-1AA42-0BA0 — Mechanical
ParameterValue
Height158 mm
Width140 mm
Depth70 mm

Product details

What this part is — and isn't

The Siemens 3VA1225-1AA42-0BA0 is a SENTRON switch disconnector in an MCCB-style frame, rated for a continuous current Iu of 250 A across 4 poles. It is not a circuit breaker — there is no overload or short-circuit trip mechanism built in.

Undervoltage release and control wiring

This unit ships with an undervoltage release (UVR) designed for 24 V DC control. When control voltage drops below the dropout threshold, the release trips the disconnect open — standard practice for emergency-stop chains or undervoltage protection schemes where a loss of control power must isolate the load. The UVR does not have a leading contact, so sequence timing for downstream contactors needs to be handled externally. The disconnect also accepts an optional motor drive for remote operation, though no auxiliary contacts are included on this variant.

Panel fit and wiring

The 3VA1225-1AA42-0BA0 occupies a 140 mm wide, 158 mm tall, 70 mm deep footprint. Main circuit connections are busbar-type front terminals.

Frequently asked questions

What is 3VA1225-1AA42-0BA0 used for?

It is a 4-pole switch disconnector rated for 250 A continuous current, used for manual load isolation and maintenance disconnect in industrial panels. It does not provide overload or short-circuit protection.

Will 3VA1225-1AA42-0BA0 fit in a panel designed for 5SQ2670-2YA63?

No. The 5SQ2670-2YA63 is a 63 A miniature circuit breaker with a 55 mm depth and C-curve trip; the 3VA1225 is a 250 A switch disconnector with a 70 mm depth and no trip function. Different footprint, different busbar interface, different protection role.

MPN