Skip to main content
Siemens 3VA1225-1AA42-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-1AA42-0BA0 SENTRON Switch Disconnector, 250

MPN3VA1225-1AA42-0BA0

Siemens SENTRON 3VA1225-1AA42-0BA0, switch disconnector in MCCB design, 4-pole, In=250 A, without overload or short-circuit protection, with undervoltage release (UVR) 24 V DC, busbar connection, front terminal.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1225-1AA42-0BA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1225-1AA42-0BA0 — Ratings
ParameterValue
Number of poles4
Power loss, max.57 W
3VA1225-1AA42-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1225-1AA42-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1225-1AA42-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1225-1AA42-0BA0 — Mechanical
ParameterValue
Height158 mm
Width140 mm
Depth70 mm

Product details

It is not a circuit breaker — there is no overload or short-circuit trip mechanism built in.

Undervoltage release and control wiring

The UVR does not have a leading contact, so sequence timing for downstream contactors needs to be handled externally. The disconnect also accepts an optional motor drive for remote operation, though no auxiliary contacts are included on this variant.

The 3VA1225-1AA42-0BA0 occupies a 140 mm wide, 158 mm tall, 70 mm deep footprint. Main circuit connections are busbar-type front terminals.

Frequently asked questions

What is 3VA1225-1AA42-0BA0 used for?

It is a 4-pole switch disconnector rated for 250 A continuous current, used for manual load isolation and maintenance disconnect in industrial panels. It does not provide overload or short-circuit protection.

Will 3VA1225-1AA42-0BA0 fit in a panel designed for 5SQ2670-2YA63?

No. The 5SQ2670-2YA63 is a 63 A miniature circuit breaker with a 55 mm depth and C-curve trip; the 3VA1225 is a 250 A switch disconnector with a 70 mm depth and no trip function. Different footprint, different busbar interface, different protection role.

MPN