Skip to main content
Siemens 3VA1225-1AA42-0DH0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1225-1AA42-0DH0 Switch Disconnector, 250

MPN3VA1225-1AA42-0DH0

Siemens SENTRON 3VA1225-1AA42-0DH0, switch disconnector in MCCB design, 4-pole, rated continuous current 250 A, with undervoltage release 208-230 V AC 50/60 Hz, 2 auxiliary switches + 1 trip alarm switch HQ, busbar connection front terminal.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1225-1AA42-0DH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design

Ratings

3VA1225-1AA42-0DH0 — Ratings
ParameterValue
Number of poles4
Power loss, max.57 W

Construction & Connection

3VA1225-1AA42-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1225-1AA42-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1225-1AA42-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1225-1AA42-0DH0 — Mechanical
ParameterValue
Height158 mm
Width140 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1225-1AA42-0DH0 is a 4-pole switch disconnector in MCCB design rated for 250 A continuous current (Iu). It provides no overload or short-circuit protection — it's a disconnect-only device, meant for isolating a circuit under load or for use as a main switch where downstream protection handles the fault clearing. Rated operational voltage is 690 V AC (50/60 Hz) and 600 V DC, with an insulation voltage (Ui) of 800 V. That puts it solidly in the 400 V / 480 V industrial panel range, with headroom for 690 V systems. The built-in undervoltage release (UVR) operates on 208-230 V AC 50/60 Hz. If control voltage drops, the UVR trips the disconnector open — a common safety requirement for motor circuits or emergency-stop chains where loss of control power should drop the load.

Dimensions are 140 mm wide, 158 mm high, 70 mm deep. The main circuit connects via busbar connection at the front terminals — typical for panel-mount MCCB-style disconnectors on a busbar system. IP40 on the front keeps dust out of the enclosure face; the back and sides rely on the panel enclosure for ingress protection. Auxiliary contact block provides 2 auxiliary switches (CO contacts) plus 1 trip alarm switch (HQ). The trip alarm signals when the disconnector has opened due to a fault or UVR trip — useful for remote status monitoring on a PLC input.

Frequently asked questions

How do I get current pricing and availability for 3VA1225-1AA42-0DH0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 3VA1225-1AA42-0DH0 drop into a panel that was specified around 5SQ2670-2YA63 without rewiring?

No — the 5SQ2670-2YA63 is a 63 A MCB (miniature circuit breaker) with IP20 and a different form factor (55 mm depth, DIN-rail mount). The 3VA1225-1AA42-0DH0 is a 250 A MCCB-style switch disconnector with busbar front terminals and IP40. They are not mechanically or electrically interchangeable.

What compliance documentation does this brand provide for 3VA1225-1AA42-0DH0?

The SENTRON series from Siemens typically carries CE, UL, CSA, and IEC certifications. Specific documentation (RoHS, REACH, UL, IEC) should be confirmed at quote time with the supplier.

MPN
3VA1225-1AA42-0DH0