Skip to main content
Siemens 3VA1225-1AA42-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-1AA42-0KC0 SENTRON Switch Disconnector, 250

MPN3VA1225-1AA42-0KC0

Siemens SENTRON 3VA1225-1AA42-0KC0, switch disconnector in MCCB design, 4-pole, In=250 A, 690 V AC / 600 V DC, with shunt trip (STL) 220-250 V DC / 208-277 V AC, 2 auxiliary switches HQ, busbar connection, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1225-1AA42-0KC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design

Ratings

3VA1225-1AA42-0KC0 — Ratings
ParameterValue
Number of poles4
Power loss, max.57 W

Construction & Connection

3VA1225-1AA42-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1225-1AA42-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1225-1AA42-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1225-1AA42-0KC0 — Mechanical
ParameterValue
Height158 mm
Width140 mm
Depth70 mm

Product details

What this 250 A switch disconnector is for

The Siemens SENTRON 3VA1225-1AA42-0KC0 is a 4-pole switch disconnector built in the MCCB frame format — rated for 250 A continuous current (Iu) and 690 V AC / 600 V DC maximum operational voltage. It provides visible-break isolation for a load circuit without overcurrent or short-circuit protection, so it is the disconnect ahead of a downstream protected feeder or a motor branch. The 250 A frame size suits larger sub-distribution boards, industrial machine infeed sections, or UPS bypass paths where you need a service-rated switch, not a breaker.

Key ratings and what they mean for fit

The 250 A rated continuous current (Iu) is the uninterrupted current the disconnector can carry without exceeding its temperature rise limits — size your upstream cable and busbar for at least this ampacity. The 690 V AC and 600 V DC maximum operational voltages mean it can isolate circuits at common industrial voltage levels, including 400/480 V three-phase and 500 V DC bus systems. Short-time withstand is 3 kA for 0.5 s and 1 s (the part can hold closed under fault current for that duration to allow a downstream breaker to clear). The 57 W maximum power loss at rated current matters for enclosure thermal calculations — if you pack several of these in a sealed panel, that heat adds up.

Integrated shunt trip and auxiliary contacts

This variant ships with a factory-fitted shunt trip (STL) release rated 220-250 V DC / 208-277 V AC, allowing remote tripping from a safety circuit or emergency-stop chain. It also includes 2 form-C auxiliary switches (HQ designation — high mechanical endurance) for status feedback to a PLC or indication lamp. The auxiliary contacts share the same mechanical endurance as the main switch: 15,000 latching operations. No undervoltage release is fitted, so the switch holds in regardless of control voltage presence — if you need a UVR for anti-restart protection, this is not the variant.

Physical integration and mounting

The disconnector measures 140 mm wide × 158 mm high × 70 mm deep — a 4-pole MCCB footprint that mounts via the front terminals (busbar connection type) for bolted busbar or cable lug landing. IP40 protection on the front face means it is protected against tools and wires >1 mm, but not against water ingress; install in a cabinet with at least an IP54 enclosure if the panel sees washdown. Operating temperature range is -25 °C to +70 °C, storage from -40 °C to +80 °C, covering most indoor industrial environments.

Frequently asked questions

Where can I buy 3VA1225-1AA42-0KC0?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote.

Does 3VA1225-1AA42-0KC0 provide overcurrent or short-circuit protection?

No — this is a switch disconnector only, without overload or short-circuit protection elements. It is designed for isolation and switching of a circuit that is protected upstream or downstream by a separate breaker or fuse.

What voltage ratings does this disconnector support?

Maximum rated operational voltage is 690 V AC (50/60 Hz) and 600 V DC. Rated insulation voltage is 800 V.

What is the closest functional alternative to 3VA1225-1AA42-0KC0?

The 3VA1010-2ED32-0JC0 is a 3-pole 100 A molded case circuit breaker in the same SENTRON 3VA family with the same 15,000-cycle endurance and shunt trip option, but it includes overcurrent protection (TM210 release) and lacks the 4th pole — it is a breaker, not a disconnector, so it cannot serve as a visible-break isolator. The 3VA1225-1AA42-0KC0 is the correct part when you need a 4-pole 250 A switch disconnector without protection.

MPN
3VA1225-1AA42-0KC0