Skip to main content
Siemens 3VA1225-4EF32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-4EF32-0JC0 SENTRON MCCB, 250 A, 3-Pole, Line

MPN3VA1225-4EF32-0JC0

Siemens SENTRON 3VA1225-4EF32-0JC0, molded case circuit breaker, 3-pole, 250 A rated continuous current, line protection, 70 mm depth, 105 mm width, 158 mm height.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1225-4EF32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1225-4EF32-0JC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C243.3 A
Current at 60 °C236.5 A
Current at 65 °C229 A
Current at 70 °C223 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V25 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1225-4EF32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1225-4EF32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1225-4EF32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1225-4EF32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1225-4EF32-0JC0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

The Siemens 3VA1225-4EF32-0JC0 is a SENTRON molded case circuit breaker (MCCB) rated for 250 A continuous current (Iu) across 3 poles, configured for line protection — meaning it sits at the feeder or main distribution point, not downstream on a motor branch. It carries a TM240 thermal-magnetic overcurrent release, so the thermal pickup is fixed at 250 A and the magnetic trip threshold is 240 A (the TM240 designation). The interrupting ratings climb to 121 kA at 240 V, 75.6 kA at 415 V, 25 kA at 440 V, and 11.9 kA at 690 V — those numbers tell you the fault-clearing capability at each voltage level, and the 415 V figure is the one most European 400 V distribution panels care about. This MCCB includes a shunt trip (STL) auxiliary release for remote tripping, plus 2 auxiliary switches (HQ type) for status feedback to a PLC or panel lamp. It does not carry undervoltage release, phase failure detection, ground fault monitoring, or communication functions — it is a straightforward thermal-magnetic breaker with a voltage-trigger capability. The front face is rated IP40, so it is protected against tools and small wires entering the enclosure but not against water ingress; mount it inside a panel, not in a washdown zone.

Thermal derating and endurance

The 250 A continuous rating holds flat from 40 °C to 50 °C ambient — no derating needed in a typical 40 °C panel. Above that, it steps down: 243.3 A at 55 °C, 236.5 A at 60 °C, 229 A at 65 °C, and 223 A at 70 °C. If your panel runs hot (e.g., inside a non-ventilated enclosure near transformers), use the 55 °C or 60 °C figure for sizing; the breaker will still carry load but at a reduced limit. Mechanical endurance is rated at 15,000 operations — that is the latching endurance, not the electrical endurance under load, so it is fine for infrequent switching but not a daily disconnect.

Physical fit and integration

The 3VA1225-4EF32-0JC0 measures 70 mm deep, 105 mm wide, and 158 mm tall. The 105 mm width is the standard 3-pole MCCB footprint for this SENTRON frame — it occupies three 35 mm DIN-rail modules (3 x 35 mm). Depth of 70 mm means it will clear most standard enclosure backplates and gland plates, but check the busbar or cable entry clearance if you are retrofitting into a shallow panel. The storage temperature range (-40 °C to 80 °C) and operating range (-25 °C to 70 °C) cover most indoor and unheated warehouse conditions.

Frequently asked questions

How do I get current pricing and availability for 3VA1225-4EF32-0JC0?

Submit an RFQ against this order code; we source through independent distribution and can confirm current pricing and stock availability at the time of quotation.

What are the key interrupting ratings for 3VA1225-4EF32-0JC0?

It is rated 121 kA at 240 V, 75.6 kA at 415 V, 25 kA at 440 V, and 11.9 kA at 690 V — the 415 V figure is the one most relevant for 400 V distribution panels.

What is the continuous current rating and thermal derating for this MCCB?

Rated continuous current Iu is 250 A, holding flat from 40 °C to 50 °C ambient. Above that it derates: 243.3 A at 55 °C, 236.5 A at 60 °C, 229 A at 65 °C, and 223 A at 70 °C.

MPN
3VA1225-4EF32-0JC0