Siemens SENTRON 3VA1225-4EF42-0AG0 — 250 A MCCB, 4-Pole, TM240 Release
Breaking capacity varies with system voltage: 121 kA at 240 V, 75.6 kA at 415 V, 25 kA at 440 V, and 11.9 kA at 690 V. Thermal derating is published per the spec table: the breaker holds 250 A from 40 °C through 50 °C, then steps down to 243.3 A at 55 °C, 236.5 A at 60 °C, 229 A at 65 °C, and 223 A at 70 °C.
Sourcing & Lifecycle — Active Production, Quoted to Order
Front-face protection is IP40, which keeps tools and fingers out but does not seal against moisture — the breaker belongs in a closed panel, not a washdown zone.