Breaking capacity drops with system voltage: 75.6 kA at 415 V, 52.5 kA at 440 V, 17 kA at 500 V, and 11.9 kA at 690 V — so verify the available fault current at your service voltage before committing the BOM line. That 250 A frame rating means this breaker can be applied in a panel with ambient up to 50 °C without derating the main conductors.
Built-in undervoltage release
If line voltage drops below the release threshold, the breaker trips, protecting downstream loads from brownout damage. No separate UVR module to wire in; it's factory-fitted. The auxiliary switch complement is 4 HQ switches, giving status feedback for remote monitoring or PLC inputs.