Breaking capacity hits 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V — that range covers most industrial distribution bus voltages without needing a current-limiting upstream breaker. Rated insulation voltage is 800 V, and the breaker operates from -25 °C to 70 °C ambient, with storage from -40 °C to 80 °C.
The basic switch module is order code 3VA12255EF320AA0; the auxiliary release is an undervoltage release (UVR), wired separately from the main power path.