Skip to main content
Siemens 3VA1225-5EF32-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-5EF32-0CA0 SENTRON MCCB, 250 A, 187 kA at 24

MPN3VA1225-5EF32-0CA0

Siemens SENTRON 3VA1225-5EF32-0CA0, molded case circuit breaker, 3-pole, 250 A rated continuous current, 187 kA breaking capacity at 240 V, TM240 thermal-magnetic release, line protection version.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1225-5EF32-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1225-5EF32-0CA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C243.3 A
Current at 60 °C236.5 A
Current at 65 °C229 A
Current at 70 °C223 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V36 kA
Breaking capacity at 690 V17 kA

Protection & Trip Unit

3VA1225-5EF32-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1225-5EF32-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1225-5EF32-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1225-5EF32-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1225-5EF32-0CA0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

Siemens SENTRON 3VA1225-5EF32-0CA0 — 250 A MCCB with TM240 release

The Siemens SENTRON 3VA1225-5EF32-0CA0 is a 3-pole molded case circuit breaker rated for 250 A continuous current (Iu) at 40 °C ambient, with a TM240 thermal-magnetic overcurrent release. It carries a breaking capacity of 187 kA at 240 V AC and 121 kA at 415 V AC — figures that place it in the high-interrupting category for industrial distribution panels where fault currents exceed typical 50–65 kA ranges. The 70 mm depth and 105 mm width fit standard SENTRON mounting footprints, so it swaps into existing 3VA panel layouts without re-drilling the backplate. This is the line protection version, meaning it is configured for feeder and main breaker duty rather than motor branch-circuit protection. The TM240 release provides fixed thermal and magnetic trip settings — no interchangeable rating plugs — so the 250 A frame is the only continuous-current option for this order code. An undervoltage release (UVR) is integrated; the auxiliary trip accessory is order code 3VA9608-0BB24. There is no auxiliary contact, no communication module, and no ground-fault monitoring on this variant.

Breaking capacity and thermal derating

The interrupting ratings span four voltage levels: 187 kA at 240 V, 121 kA at 415 V, 36 kA at 440 V, and 17 kA at 690 V (–). At 415 V, 121 kA exceeds the typical 50–65 kA SCCR found in most North American panel schedules — this breaker is sized for high-fault installations such as transformer secondaries or large motor control centers where the available fault current is known to be above 100 kA. The rated insulation voltage (Ui) is 800 V, confirming the 690 V rating is within the device's insulation coordination. Thermal derating begins at 55 °C: the breaker carries the full 250 A up to 50 °C (–), then steps down to 243.3 A at 55 °C, 236.5 A at 60 °C, 229 A at 65 °C, and 223 A at 70 °C (–). The operating ambient range is -25 °C to +70 °C (–); storage range is -40 °C to +80 °C (–). For a panel that runs at 60 °C internal ambient, the usable current is 236.5 A — a 5.4 % reduction from the nameplate rating.

Panel integration and mechanical notes

The breaker measures 105 mm wide, 158 mm high, and 70 mm deep (–). It mounts on a DIN rail or directly to a backplate via the SENTRON mounting base. The front face carries an IP40 protection class, suitable for enclosed panel installation where no water spray is present. Latching endurance is rated at 15,000 cycles — sufficient for main breaker duty where switching events are infrequent. There is no trip indicator on the front, so a remote indication requires the auxiliary contact accessory (not included).

Frequently asked questions

How do I get pricing and availability for 3VA1225-5EF32-0CA0?

This part is sourced to order against an RFQ through independent distribution. Current pricing and availability are confirmed at quote time.

What is the breaking capacity of 3VA1225-5EF32-0CA0 at 415 V?

The breaking capacity is 121 kA at 415 V AC. It also carries 187 kA at 240 V, 36 kA at 440 V, and 17 kA at 690 V.

Does 3VA1225-5EF32-0CA0 include an undervoltage release?

Yes, it is equipped with an undervoltage release (UVR) as standard. The auxiliary trip accessory is order code 3VA9608-0BB24.

MPN
3VA1225-5EF32-0CA0