This MCCB delivers 187 kA breaking capacity at 240 V, 121 kA at 415 V, 36 kA at 440 V, and 17 kA at 690 V. The 4-pole design (three phases plus neutral switched) is standard for TN-S or TT systems where the neutral needs disconnection.
At 55 °C it derates to 243.3 A, at 60 °C to 236.5 A, at 65 °C to 229 A, and at 70 °C to 223 A. That means in a warm panel — say 50 °C internal — you still get full 250 A; above that, the thermal element trips earlier to protect the breaker internals. The IP40 front protection is typical for panel-mounted breakers — dust-protected but not sealed against water ingress.
Auxiliary contacts and signaling
The trip alarm signals a fault trip separately from manual on/off status — useful for remote monitoring or PLC input.
