Current derating and thermal management
Full 250 A rating holds from 40 °C through 50 °C; above that it derates linearly to 223 A at 70 °C. Maximum power loss is 59.5 W — account for that heat in the enclosure sizing, especially in a sealed cabinet with multiple breakers side by side.
Breaking capacity by voltage
Interrupting rating drops as system voltage rises: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V.