MCCB with line protection focus
The Siemens SENTRON 3VA1225-5EF42-0KC0 is a 4-pole molded case circuit breaker rated 250 A at 40 °C, designed for line protection in distribution panels. Its interrupting capacity reaches 187 kA at 240 V and 121 kA at 415 V, meaning it can safely clear high-fault currents without upstream coordination failure — critical for main breaker or large feeder applications where available fault current is high.
Thermal derating and power loss
The breaker holds 250 A continuously up to 50 °C ambient; above that it derates to 243 A at 55 °C and 223 A at 70 °C. Maximum power loss is 57 W — a factor for enclosure heat rise calculations when multiple breakers are ganged in a panel.
Auxiliary and shunt trip options
Factory-fitted with 2 auxiliary switches (HQ type) and a shunt trip release (STL) for remote tripping. No undervoltage release or ground-fault monitoring on this variant — those are separate order-code options. The auxiliary switches provide status feedback to a PLC or alarm panel.