Skip to main content
Siemens 3VA1225-5FF42-0CC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-5FF42-0CC0 SENTRON MCCB, 125 A, 4-Pole, 187

MPN3VA1225-5FF42-0CC0

Siemens SENTRON 3VA1225-5FF42-0CC0, molded case circuit breaker, 4-pole, 125 A fixed rating, line protection, 187 kA breaking capacity at 240 V AC, with undervoltage release and 2 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1225-5FF42-0CC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12255FF420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1225-5FF42-0CC0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C243 A
Current at 60 °C237 A
Current at 65 °C230 A
Current at 70 °C223 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.59.5 W
3VA1225-5FF42-0CC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1225-5FF42-0CC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1225-5FF42-0CC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1225-5FF42-0CC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1225-5FF42-0CC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width140 mm
Depth70 mm
Height (in)6.22 in
Width (in)5.51 in
Depth (in)2.76 in

Product details

Integrator note — 125 A fixed, 4-pole, line protection

Breaking capacity scales with system voltage: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, 17 kA at 690 V. Rated insulation voltage 800 V.

Thermal derating — continuous current vs ambient

Full 125 A holds through 50 °C ambient. Above that it steps down: 243 A at 55 °C, 237 A at 60 °C, 230 A at 65 °C, 223 A at 70 °C. If the panel sits near a heat source or in a non-conditioned enclosure, use the 55 °C or 60 °C column for sizing.

Integrated auxiliaries — what comes on the breaker

Envelope: 158 mm height, 140 mm width, 70 mm depth. The supplied basic switch variant is 3VA12255FF420AA0 — that's the bare breaker core; this order code adds the UVR and aux switches in one configurable assembly.

Frequently asked questions

How do I get current pricing and availability for 3VA1225-5FF42-0CC0?

Submit an RFQ — the part is sourced to order through independent distribution, with pricing and stock confirmed at quote time.

What is 3VA1225-5FF42-0CC0's listed depth?

Depth is 70 mm (2.76 in). Height 158 mm, width 140 mm.

What is 3VA1225-5FF42-0CC0's breaking capacity at 415 V?

121 kA at 415 V AC. Also rated 187 kA at 240 V, 75.6 kA at 440 V, 30 kA at 500 V, 17 kA at 690 V.

Does 3VA1225-5FF42-0CC0 include an undervoltage release?

Yes, factory-fitted with an undervoltage release (UVR) plus two HQ auxiliary switches.

MPN
3VA1225-5FF42-0CC0