Siemens 3VA1225-5FF42-0DH0 — 125 A SENTRON MCCB for Line Protection
Its interrupting capacity reaches 187 kA at 240 V, 121 kA at 415 V, and 75.6 kA at 440 V — figures that govern selectivity coordination with downstream breakers.
The breaker carries 250 A up to 50 °C ambient, then derates linearly: 243 A at 55 °C, 237 A at 60 °C, 230 A at 65 °C, and 223 A at 70 °C (–). Maximum power loss is 59.5 W — relevant for enclosure heat-rise calculations when grouping multiple breakers in a panel.
Auxiliary Switching and Releases
The trip indicator provides local visual status. The basic switch variant is 3VA12255FF420AA0.