Skip to main content
Siemens 3VA1225-6EF32-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-6EF32-0HH0 SENTRON MCCB, 250A, 3-Pole, 220kA

MPN3VA1225-6EF32-0HH0

Siemens SENTRON 3VA1225-6EF32-0HH0, molded case circuit breaker, 3-pole, 250 A at 40 °C, 220 kA breaking capacity at 240 V, line protection design, shunt trip release, 2 auxiliary switches + 1 trip alarm switch HQ.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1225-6EF32-0HH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12256EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1225-6EF32-0HH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C243 A
Current at 60 °C237 A
Current at 65 °C230 A
Current at 70 °C223 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.57 W

Protection & Trip Unit

3VA1225-6EF32-0HH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1225-6EF32-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1225-6EF32-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1225-6EF32-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1225-6EF32-0HH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width105 mm
Depth70 mm
Height (in)6.22 in
Width (in)4.13 in
Depth (in)2.76 in

Product details

Siemens 3VA1225-6EF32-0HH0 — 250 A MCCB with line protection and shunt trip

The Siemens 3VA1225-6EF32-0HH0 is a SENTRON molded case circuit breaker (MCCB) rated for 250 A at 40 °C, with a 3-pole configuration and a breaking capacity of 220 kA at 240 V. Designed for line protection, it integrates a shunt trip (STL) release and comes with 2 auxiliary switches plus 1 trip alarm switch HQ. The 800 V rated insulation voltage supports 400 V and 690 V distribution systems common in industrial panels. At 57 W maximum power loss, this MCCB runs cool enough for high-density DIN-rail or panel-mount layouts where heat buildup from multiple breakers can derate adjacent components. The 70 mm depth (2.76 in) and 105 mm width (4.13 in) fit standard Siemens 3VA mounting footprints — no panel rework needed when swapping from an earlier 3VA frame.

Breaking capacity and thermal derating — what the ratings mean

The 220 kA at 240 V is the maximum prospective fault current this breaker can safely interrupt at that voltage level — critical for high-fault locations like transformer secondaries or large motor control centers. At 415 V the rating drops to 154 kA, at 440 V to 75.6 kA, at 500 V to 30 kA, and at 690 V to 17 kA. These values govern selectivity coordination downstream: a 220 kA SCCR at 240 V means the breaker clears faults up to that threshold without upstream devices needing to trip. Thermal derating is flat at 250 A from 40 °C through 50 °C, then steps down: 243 A at 55 °C, 237 A at 60 °C, 230 A at 65 °C, and 223 A at 70 °C. For a panel running at 60 °C ambient — common in sealed enclosures with multiple breakers — the usable continuous current is 237 A, not 250 A. Plan the load at the derated figure, not the 40 °C nameplate.

Integration — panel fit and auxiliary wiring

Mounts on a DIN rail or direct-panel via the 3VA base plate. The 105 mm width occupies three 35 mm DIN spaces (3 x 35 mm = 105 mm) — standard for a 3-pole MCCB this frame size. Depth of 70 mm leaves clearance for rear-access busbars and cable glands on a 200 mm deep enclosure. Auxiliary switch configuration is 2 auxiliary switches + 1 trip alarm switch HQ. The shunt trip (STL) release is factory-fitted; no field kit needed. The supplied basic switch variant is 3VA12256EF320AA0 — verify the trip indicator (present) and undervoltage release (absent) match your safety circuit design. Communication function is not built in; this is a standalone thermal-magnetic breaker.

MPN
3VA1225-6EF32-0HH0