Skip to main content
Siemens 3VA1225-6EF42-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1225-6EF42-0AH0 MCCB, 250 A, 4-Pole, TM24

MPN3VA1225-6EF42-0AH0

Siemens SENTRON 3VA series, molded case circuit breaker, 4-pole, 250 A (40-50 °C), TM240 thermal-magnetic release, 220 kA at 240 V AC, 70 x 140 x 158 mm.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1225-6EF42-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA12256EF420AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1225-6EF42-0AH0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C243 A
Current at 60 °C237 A
Current at 65 °C230 A
Current at 70 °C223 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V30 kA
Breaking capacity at 690 V17 kA
Power loss, max.57 W

Protection & Trip Unit

3VA1225-6EF42-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1225-6EF42-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1225-6EF42-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1225-6EF42-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1225-6EF42-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height158 mm
Width140 mm
Depth70 mm
Height (in)6.22 in
Width (in)5.51 in
Depth (in)2.76 in

Product details

SENTRON 3VA1225-6EF42-0AH0 — 250 A Molded Case Circuit Breaker, 4-Pole, TM240 Release

The Siemens SENTRON 3VA1225-6EF42-0AH0 is a 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 250 A across its 40 °C to 50 °C ambient range — no derating needed up to that point (cites:,). Above 50 °C it derates linearly to 223 A at 70 °C (cites:,). The TM240 thermal-magnetic release provides fixed overload and short-circuit protection curves, with a trip indicator for visual fault confirmation (cites:,). Breaking capacity reaches 220 kA at 240 V AC, stepping down to 154 kA at 415 V, 75.6 kA at 440 V, 30 kA at 500 V, and 17 kA at 690 V — sufficient for high-fault utility feeds and transformer secondaries (cites:,). Rated insulation voltage is 800 V, giving headroom for 690 V line-to-line systems (cites:).

Panel Fit and Auxiliary Wiring

At 70 mm deep, 140 mm wide, and 158 mm tall, this MCCB occupies a standard SENTRON 3VA footprint — expect a 4-pole unit to span roughly 9 module widths on a DIN rail or direct-mount plate (cites:,). The auxiliary switch configuration is factory-fitted: two auxiliary contacts plus one trip alarm switch (HQ type), eliminating the need for a separate add-on module for basic status feedback (cites:). Power dissipation at rated load reaches 57 W maximum — factor that into enclosure thermal calculations, especially in sealed, high-fill panels (cites:). The breaker is designed without undervoltage release, ground-fault monitoring, or communication function, so those features must be added externally if required (cites:,).

Operating Environment and Storage

Rated for operation from -25 °C to 70 °C ambient, with storage range from -40 °C to 80 °C (cites:,). The storage limits exceed the operating range — that governs handling and warehousing, not running conditions. The thermal derating curve above 50 °C is the binding constraint for continuous load in warm enclosures.

Frequently asked questions

What is the breaking capacity of 3VA1225-6EF42-0AH0 at 415 V?

At 415 V AC, the rated ultimate breaking capacity (Icu) is 154 kA (cites:). At 240 V it reaches 220 kA, and at 690 V it is 17 kA (cites:,).

What does the TM240 release designation mean on this MCCB?

TM240 indicates a thermal-magnetic release with a fixed current rating of 240 A — the breaker frame is rated 250 A, and the TM240 release sets the continuous current threshold at 240 A, with magnetic trip for short-circuit protection (cites:,).

Where can I buy 3VA1225-6EF42-0AH0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent industrial distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
3VA1225-6EF42-0AH0