Siemens 3VA1225-6EF42-0CA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-6EF42-0CA0 SENTRON MCCB, 250 A, 4-Pole, Line

MPN3VA1225-6EF42-0CA0

Siemens SENTRON 3VA1225-6EF42-0CA0, molded case circuit breaker, 4-pole, 250 A rated continuous current, TM240 overcurrent release, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1225-6EF42-0CA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1225-6EF42-0CA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C243.3 A
Current at 60 °C236.5 A
Current at 65 °C229 A
Current at 70 °C223 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V36 kA
Breaking capacity at 690 V17 kA
3VA1225-6EF42-0CA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1225-6EF42-0CA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1225-6EF42-0CA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1225-6EF42-0CA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1225-6EF42-0CA0 — Mechanical
ParameterValue
Height158 mm
Width140 mm
Depth70 mm

Product details

Its TM240 thermal-magnetic release handles overloads and short-circuits up to 220 kA at 240 V, 154 kA at 415 V, 36 kA at 440 V, and 17 kA at 690 V — meaning it can interrupt fault currents at the main breaker level without upstream coordination issues. The 250 A rating holds flat from 40 °C to 50 °C, then derates to 243.3 A at 55 °C, 236.5 A at 60 °C, 229 A at 65 °C, and 223 A at 70 °C — so in a warm enclosure you lose roughly 11% capacity at the top of the operating range.

Frequently asked questions

Does this breaker include an undervoltage release?

Yes, it is equipped with an undervoltage release (UVR) designated as 3VA9608-0BB24, which trips the breaker on loss of control voltage.

MPN
3VA1225-6EF42-0CA0