Four poles cover three-phase plus neutral, and the shunt trip (STL) allows remote tripping. Breaking capacity hits 220 kA at 240 V, 154 kA at 415 V, 36 kA at 440 V, and 17 kA at 690 V — so it handles high-fault utility feeds and transformer secondaries.
Current rating across the panel ambient range
At 55 °C it derates to 243.3 A, at 60 °C to 236.5 A, at 65 °C to 229 A, and at 70 °C to 223 A.