Skip to main content
Siemens 3VA1225-6EF42-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1225-6EF42-0KC0 SENTRON MCCB, 250 A, 220 kA

MPN3VA1225-6EF42-0KC0

Siemens SENTRON 3VA1225-6EF42-0KC0, 4-pole molded case circuit breaker, 250 A rated continuous current, 220 kA breaking capacity at 240 V, line protection, TM240 overcurrent release, 2 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1225-6EF42-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1225-6EF42-0KC0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C250 A
Current at 45 °C250 A
Current at 50 °C250 A
Current at 55 °C243.3 A
Current at 60 °C236.5 A
Current at 65 °C229 A
Current at 70 °C223 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V36 kA
Breaking capacity at 690 V17 kA
3VA1225-6EF42-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1225-6EF42-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1225-6EF42-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1225-6EF42-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1225-6EF42-0KC0 — Mechanical
ParameterValue
Height158 mm
Width140 mm
Depth70 mm

Product details

Its 220 kA breaking capacity at 240 V handles high-fault scenarios typical of large transformer secondaries or bus-tie applications — the interrupting rating drops to 154 kA at 415 V and 36 kA at 440 V, so selectivity studies need to account for the actual system voltage.

The TM240 thermal-magnetic release provides fixed overload and short-circuit protection with no field-adjustable trip curve, so coordination with downstream breakers must be verified at the design stage.

Frequently asked questions

How do I get current pricing and availability for 3VA1225-6EF42-0KC0?

Submit an RFQ through this listing; pricing and stock are confirmed at quote time through independent distribution channels.

What are the key ratings of this MCCB?

Rated continuous current 250 A, breaking capacity 220 kA at 240 V, 154 kA at 415 V, 36 kA at 440 V, and 17 kA at 690 V. It is a 4-pole line-protection device with a TM240 thermal-magnetic release and two auxiliary switches HQ.

MPN